Flexible insulated conductor used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 1000 V alternating current, or up to 750 V direct current against earth.

Flexible, Max cinductor temperature 70, Min installation temperature -5, Nominal Voltage 450-750V
specs
Constructional Wires
Electrical Specs:
Code No | conductor cross-section | Construction of individual conductor | External diameter | Insulation thickness | Conductor resistance at 20 °C | Cable weight | Packing* |
mm² | nominal n x mm |
min-max. mm |
nominal mm |
max. Ω/km |
approx. kg/km | ||
1175 | 0.75 | 24 x 0,195 | 2,0 – 2.4 | 0,6 | 26 | 12 | c.100, c.200 |
1110 | 1.0 | 31 x 0,195 | 2.3 – 2.7 | 0.6 | 19.5 | 15 | c.100, c.200 |
1115 | 1.5 | 30 x 0,25 | 2,8 – 3.4 | 0.7 | 13.3 | 20 | c.100, c.200 |
1125 | 2.5 | 50 x 0,25 | 3,4 – 3.6 | 0.8 | 7.98 | 32 | c.100 |
1140 | 4 | 56 x 0,30 | 3,9 - 4,3 | 0.8 | 4.95 | 46 | c.100 |
1160 | 6 | 84 x 0,30 | 4,5 – 4.9 | 0.8 | 3.30 | 65 | c.100 |
1110 | 10 | 80 x 0,40 | 5,7 - 6,1 | 1,0 | 1.91 | 115 | c.100 |
11160 | 16 | 128 x 0,40 | 6,8 – 7.2 | 1,0 | 1.21 | 170 | c.100 |
11250 | 25 | 200 x 0,40 | 8,8 – 9.2 | 1,2 | 0,780 | 260 | CUT |
11350 | 35 | 280 x 0,40 | 10.4 – 10.8 | 1,2 | 0,554 | 360 | CUT |
11500 | 50 | 400 x 0,40 | 12.2 – 12.6 | 1,4 | 0,386 | 515 | CUT |
11700 | 70 | 356 x 0,50 | 13,3 – 13.7 | 1,4 | 0,272 | 710 | CUT |
11950 | 95 | 485 x 0,50 | 16.2 – 16.9 | 1,6 | 0,206 | 940 | CUT |
111200 | 120 | 614 x 0,50 | 17 – 17.9 | 1.6 | 0.161 | 1180 | CUT |
111500 | 150 | 765 x 0,50 | 19.0 – 19.9 | 1.8 | 0.129 | 1600 | CUT |
111850 | 185 | 944 x 0,50 | 21.0 – 21.9 | 2.0 | 0,106 | 2100 | CUT |
112400 | 240 | 1225 x 0,50 | 24.0 – 24.9 | 2,2 | 0,0801 | 3015 | CUT |
Physical Specs:
Conductor: | bare copper conductor, fine wired stranded, class 5. acc. to IEC 60228 / HD 383 / DIN VDE 0295 | |
Insulation: | PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3 | |
Conductor color identification: | acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) |
Technical Specs:
Temperature during installation: | +5 °C up to +70 °C |
fixed installation Temperature: | -30 °C up to +70 °C |
Temperature at short circuit of max. 5 s: | up to 160 °C |
ambient temperature at storage: | up to 40 °C |
Nominal voltage: | Uο/U = 450/750 V |
Test voltage: | 2500 V |
Minimal inner bending radius: | 4D for D < 8 mm 5D for 8 - 12 mm 6D for D > 12 mm |
Behaviour in fire: | IEC 60332-1 |